Psychrometric Calculator

Humidity ratio, enthalpy, saturation pressure and density of moist air at a given state.

Results

Humidity ratio 0.009277 kg/kg
Humidity ratio 9.277 g/kg
Enthalpy 47.7592 kJ/kg
Vapour pressure 2.97807 kPa
Density 1.17042 kg/m³

What this tool does

Enthalpy is the number air conditioning is designed around, because cooling has to remove both the temperature and the moisture, and only enthalpy counts both. That is why dehumidifying costs so much: at 24 °C and 50 % relative humidity, over half the enthalpy of the air is latent heat carried by the water vapour, not sensible heat you can feel on a thermometer.

Formula

W = 0.621 98 pw ÷ (p − pw) ; h = 1.006 t + W(2501 + 1.86 t)

Variables

SymbolMeaningUnit
ttTemperature°C
rhRelative humidity%
ppAtmospheric pressurekPa
WWHumidity ratiokg/kg
GKHumidity ratiog/kg
HHEnthalpykJ/kg
PSVapour pressurekPa
DEDensitykg/m³

Worked example

  • Temperature24 °C
  • Relative humidity50 %
  • Atmospheric pressure101.325 kPa
  • Humidity ratio0.009277 kg/kg
  • Humidity ratio9.277 g/kg
  • Enthalpy47.7592 kJ/kg
  • Vapour pressure2.97807 kPa
  • Density1.17042 kg/m³