Conduit Fill Calculator (Cables in a Conduit or Trunking)

How full a conduit is with a given number of same-size cables, the fill the code allows for that number of cables, and the most cables that fit.

Results

Share of the conduit area filled 27.0 %
Fill allowed for that many cables 40 %
Most cables of that size that fit 5
Result Yes — within the fill limit

What this tool does

A conduit is not meant to be packed: cables need room to be pulled in and to shed heat. The US National Electrical Code (Chapter 9, Table 1) allows 53 % of the cross-section for a single cable, 31 % for two and 40 % for three or more — the figure drops for two because they tend to wedge. Fill is the ratio of areas, so it goes with the square of the diameters: a cable only 10 % wider takes 21 % more room. Other countries and standards set their own limits, and bundled cables may need derating, so check the rules that apply to your installation.

Formula

fill = n × (cable diameter ÷ conduit diameter)² × 100 · limits (NEC Chapter 9): 1 cable 53 %, 2 cables 31 %, 3 or more 40 %

Variables

SymbolMeaningUnit
ddInside diameter of the conduitmm
in2Number of cables—
ccOutside diameter of each cable (insulation included)mm
FLShare of the conduit area filled%
ALFill allowed for that many cables%
MXMost cables of that size that fit—
OKResult—

Worked example

  • Inside diameter of the conduit25 mm
  • Number of cables4
  • Outside diameter of each cable (insulation included)6.5 mm
  • Share of the conduit area filled27.0 %
  • Fill allowed for that many cables40 %
  • Most cables of that size that fit5
  • ResultYes — within the fill limit

Limitations

  • For work that must comply with a standard or be signed off, check the result against the applicable code and have it reviewed by a qualified engineer.
  • Electrical installations are governed by national wiring rules. Cable sizing also depends on installation method, grouping, ambient temperature and protection devices, which this calculator does not evaluate.