Heating Expansion Vessel Sizing Calculator

Volume of the expansion vessel for a closed heating or chilled-water circuit, from the system water volume, the fill and maximum temperatures and the pressures — with the water's expansion worked out from its density.

Results

Expansion vessel volume needed 20.4 L
Expansion of the water 2.87 %
Extra volume of water 5.74 L
Share of the vessel that is usable 43 %
How it changes
Expansion vessel volume neededHighest water temperature 15 – 100. Expansion vessel volume needed: 7.28026 → 27.1282Expansion vessel volume needed010203020406080100Highest water temperature (°C)

The dashed line marks the value you entered.

What this tool does

Water expands when it warms: about 2.9 % between 10 °C and 80 °C and 4.3 % by 100 °C, so a 200 L system must find room for nearly 6 litres. The vessel is a gas-filled cushion, and only part of its volume is usable because the gas is compressed from the pre-charge pressure to the maximum pressure by Boyle's law: usable share = 1 − (p_pre + 1) ÷ (p_max + 1) with pressures in bar gauge. A small water reserve keeps the vessel from being emptied as the system cools. Glycol mixtures expand more than water, and the standards add margins — this is an estimate, so check the maker's sizing.

Formula

expansion = ρ(t_fill) ÷ ρ(t_max) − 1 · V_vessel = (V_system × expansion + V_reserve) ÷ (1 − (p_pre + 1) ÷ (p_max + 1)) (pressures gauge, +1 bar for atmosphere)

Variables

SymbolMeaningUnit
vsWater in the whole systemL
t1Water temperature when filled°C
t2Highest water temperature°C
paVessel pre-charge (gauge) — about the static pressure plus a marginbar
peHighest pressure allowed (gauge), a bit under the safety valvebar
rvWater reserve to keep in the vesselL
VNExpansion vessel volume neededL
EXExpansion of the water%
VEExtra volume of waterL
UFShare of the vessel that is usable%

Worked example

  • Water in the whole system200 L
  • Water temperature when filled10 °C
  • Highest water temperature80 °C
  • Vessel pre-charge (gauge) — about the static pressure plus a margin1 bar
  • Highest pressure allowed (gauge), a bit under the safety valve2.5 bar
  • Water reserve to keep in the vessel3 L
  • Expansion vessel volume needed20.4 L
  • Expansion of the water2.87 %
  • Extra volume of water5.74 L
  • Share of the vessel that is usable43 %

Limitations

  • The result is an estimate based only on the values you type. Real situations often include factors this calculator does not know about.
  • For work that must comply with a standard or be signed off, check the result against the applicable code and have it reviewed by a qualified engineer.