Motor Full-Load Current Calculator

Estimate the full-load current of a three-phase motor from its shaft power, efficiency and power factor.

Results

Current 20.29 A
Active power 12.088 kW
Apparent power 14.056 kVA

What this tool does

A motor's nameplate power is the mechanical output at the shaft; the electrical input is larger by the efficiency. This calculator works backwards from shaft power to the current the supply actually has to deliver, which is the figure that sizes the cable and the protection.

Formula

I = P ÷ (√3 × U × cos φ × η)

Variables

SymbolMeaningUnit
pPowerkW
uLine-to-line voltageV
pfPower factor
efEfficiency%
ICurrentA
PinActive powerkW
SApparent powerkVA

Worked example

  • Power11 kW
  • Line-to-line voltage400 V
  • Power factor0.86
  • Efficiency91 %
  • Current20.29 A
  • Active power12.088 kW
  • Apparent power14.056 kVA

Limitations

  • Electrical installations are governed by national wiring rules. Cable sizing also depends on installation method, grouping, ambient temperature and protection devices, which this calculator does not evaluate.
  • The result is an estimate based only on the values you type. Real situations often include factors this calculator does not know about.