Surface Condensation and Mould Risk Calculator

Temperature of the inside face of a wall, window or corner on a cold day, and whether it will get condensation or mould at the room's humidity.

Results

Temperature of the inner surface 15.8 °C
Dew point of the room air 12.0 °C
Relative humidity right at the surface 78 %
Temperature factor fRsi 0.792
What to expect Unlikely in these conditions
How it changes
Temperature of the inner surfaceU-value of the wall, window or corner 0.1 – 3.0. Temperature of the inner surface: 19.74 → 12.2; Dew point of the room air: 11.9955 → 11.9955Temperature of the inner surfaceDew point of the room air051015200.51.01.52.02.53.0U-value of the wall, window or corner (W/(m²·K))

The dashed line marks the value you entered.

What this tool does

A poorly insulated wall is cold on the inside, and the air touching it cools down too: its relative humidity rises, and above about 80 % for a few days mould can grow even without visible water, as the European standard EN ISO 13788 assumes. At the dew point water condenses outright. Corners, window reveals and walls behind wardrobes are colder still because less warm air reaches them, which is why the larger surface resistance of 0.25 is used there. Better insulation raises the surface temperature; ventilation lowers the humidity — the chart shows how much each U-value helps.

Formula

T_si = T_i − U × R_si × (T_i − T_e) · condensation if T_si < dew point · mould risk if surface RH ≥ 80 %

Variables

SymbolMeaningUnit
tiIndoor temperature°C
rhIndoor relative humidity%
teOutdoor temperature°C
uU-value of the wall, window or cornerW/(m²·K)
rsiInner surface resistance (0.13 open wall, 0.25 corners or behind furniture)m²·K/W
TSTemperature of the inner surface°C
TDDew point of the room air°C
RSRelative humidity right at the surface%
FRTemperature factor fRsi—
VDWhat to expect—

Worked example

  • Indoor temperature20 °C
  • Indoor relative humidity60 %
  • Outdoor temperature0 °C
  • U-value of the wall, window or corner1.6 W/(m²·K)
  • Inner surface resistance (0.13 open wall, 0.25 corners or behind furniture)0.13 m²·K/W
  • Temperature of the inner surface15.8 °C
  • Dew point of the room air12.0 °C
  • Relative humidity right at the surface78 %
  • Temperature factor fRsi0.792
  • What to expectUnlikely in these conditions

Limitations

  • For work that must comply with a standard or be signed off, check the result against the applicable code and have it reviewed by a qualified engineer.
  • The result is an estimate based only on the values you type. Real situations often include factors this calculator does not know about.