Evaporative Cooler Calculator (Outlet Air Temperature)
Temperature of the air leaving a direct evaporative cooler from the outdoor temperature, humidity and the effectiveness of the wet media.
Results
The dashed line marks the value you entered.
What this tool does
A direct evaporative cooler can never cool the air below its wet-bulb temperature; its effectiveness says what share of the gap between air and wet-bulb it closes, and wetted-pad media typically reach roughly 70–90 %. So the dryer the air, the bigger the gap and the bigger the cooling: 35 °C air at 25 % humidity drops by well over 10 °C, while at 70 % humidity the same cooler gains only a few degrees. The air also leaves more humid, so the room needs an opening to let it out.
Formula
T_out = T − ε × (T − Tw) (Tw = wet-bulb temperature by Stull's formula, ε = effectiveness)
Variables
| Symbol | Meaning | Unit |
|---|---|---|
t | Temperature | °C |
rh | Relative humidity | % |
ef | Cooler effectiveness (saturation efficiency) | % |
TO | Air temperature leaving the cooler | °C |
DR | Temperature drop | °C |
TW | Wet-bulb temperature | °C |
Worked example
- Temperature35 °C
- Relative humidity25 %
- Cooler effectiveness (saturation efficiency)80 %
- Air temperature leaving the cooler23.6 °C
- Temperature drop11.4 °C
- Wet-bulb temperature20.8 °C
Limitations
- The result is an estimate based only on the values you type. Real situations often include factors this calculator does not know about.
- The formula assumes ideal conditions: no friction losses, no air resistance and no efficiency losses unless you enter them.