Three-Phase Neutral Current Calculator (Unbalanced Loads)

The current that flows in the neutral of a three-phase four-wire supply when the three phase currents are unequal, with the unbalance and the neutral as a share of the largest phase.

Results

Current in the neutral 8.66 A
Average phase current 25.00 A
Unbalance (largest deviation from the average) 20.0 %
Neutral current as a share of the largest phase 28.9 %

What this tool does

In a balanced three-phase system the three currents cancel and the neutral carries nothing; whatever is left over after cancelling is the neutral current. For loads with the same power factor on every phase the three currents sit 120° apart and the neutral current is √(I₁² + I₂² + I₃² − I₁I₂ − I₂I₃ − I₃I₁) — notably it can never exceed the largest phase current. Electronic loads such as switch-mode power supplies break this rule: their third harmonics add up in the neutral instead of cancelling, so the neutral can carry more than any phase.

Formula

I_N = √(I₁² + I₂² + I₃² − I₁I₂ − I₂I₃ − I₃I₁) (120° apart, same power factor on all three)

Variables

SymbolMeaningUnit
i1Current in phase L1A
i2Current in phase L2A
i3Current in phase L3A
INCurrent in the neutralA
AVAverage phase currentA
UBUnbalance (largest deviation from the average)%
PCNeutral current as a share of the largest phase%

Worked example

  • Current in phase L130 A
  • Current in phase L220 A
  • Current in phase L325 A
  • Current in the neutral8.66 A
  • Average phase current25.00 A
  • Unbalance (largest deviation from the average)20.0 %
  • Neutral current as a share of the largest phase28.9 %

Limitations

  • The formula assumes ideal conditions: no friction losses, no air resistance and no efficiency losses unless you enter them.
  • Electrical installations are governed by national wiring rules. Cable sizing also depends on installation method, grouping, ambient temperature and protection devices, which this calculator does not evaluate.