Three-Phase Neutral Current Calculator (Unbalanced Loads)
The current that flows in the neutral of a three-phase four-wire supply when the three phase currents are unequal, with the unbalance and the neutral as a share of the largest phase.
Results
What this tool does
In a balanced three-phase system the three currents cancel and the neutral carries nothing; whatever is left over after cancelling is the neutral current. For loads with the same power factor on every phase the three currents sit 120° apart and the neutral current is √(I₁² + I₂² + I₃² − I₁I₂ − I₂I₃ − I₃I₁) — notably it can never exceed the largest phase current. Electronic loads such as switch-mode power supplies break this rule: their third harmonics add up in the neutral instead of cancelling, so the neutral can carry more than any phase.
Formula
I_N = √(I₁² + I₂² + I₃² − I₁I₂ − I₂I₃ − I₃I₁) (120° apart, same power factor on all three)
Variables
| Symbol | Meaning | Unit |
|---|---|---|
i1 | Current in phase L1 | A |
i2 | Current in phase L2 | A |
i3 | Current in phase L3 | A |
IN | Current in the neutral | A |
AV | Average phase current | A |
UB | Unbalance (largest deviation from the average) | % |
PC | Neutral current as a share of the largest phase | % |
Worked example
- Current in phase L130 A
- Current in phase L220 A
- Current in phase L325 A
- Current in the neutral8.66 A
- Average phase current25.00 A
- Unbalance (largest deviation from the average)20.0 %
- Neutral current as a share of the largest phase28.9 %