Pump Operating Point Calculator (Pump Curve Meets System Curve)

The flow and head a pump will really deliver in a given pipe system, from its shut-off head and one rated point and the system's static head and friction loss, with both curves drawn.

Results

Flow you will actually get 62.5 m³/h
Head at the operating point 27.5 m
Hydraulic power (water) 4.68 kW
Shaft power at that point 6.69 kW
Pump head at the flow you chose 34.9 m
System head needed at the flow you chose 20.1 m
How it changes
Pump head at the flow you choseFlow at which to read the two curves 0 – 80. Pump head at the flow you chose: 40 → 19.52; System head needed at the flow you chose: 15 → 35.48Pump head at the flow you choseSystem head needed at the flow you chose010203040020406080Flow at which to read the two curves (m³/h)

The dashed line marks the value you entered.

What this tool does

A pump does not deliver its rated flow, it delivers where its own curve crosses the system curve: the static head to be overcome plus a friction loss that grows with the square of the flow. Here the pump curve is a parabola H = H₀ − aQ² through the shut-off head and one rated point, which is a good fit over the useful middle of a centrifugal pump's curve; the system curve is H = H_static + KQ². Closing a valve steepens the system curve and moves the point left; more static lift moves it left too. Keep the point near the pump's best-efficiency flow rather than far to either side.

Formula

pump curve H = H0 − a Q² · system curve H = H_static + K Q² · operating point Q = Q_r √[(H0 − H_static) ÷ ((H0 − H_r) + h_f)]

Variables

SymbolMeaningUnit
h0Pump head at zero flow (shut-off head)m
hrPump head at the rated flowm
qrRated flow (the point you took the head at)m³/h
hsStatic head (lift plus pressure to deliver against)m
hfFriction head loss in the pipework at the rated flowm
efPump efficiency at the duty point%
qFlow at which to read the two curvesm³/h
QOFlow you will actually getm³/h
HOHead at the operating pointm
PHHydraulic power (water)kW
PSShaft power at that pointkW
HPPump head at the flow you chosem
HYSystem head needed at the flow you chosem

Worked example

  • Pump head at zero flow (shut-off head)40 m
  • Pump head at the rated flow32 m
  • Rated flow (the point you took the head at)50 m³/h
  • Static head (lift plus pressure to deliver against)15 m
  • Friction head loss in the pipework at the rated flow8 m
  • Pump efficiency at the duty point70 %
  • Flow at which to read the two curves40 m³/h
  • Flow you will actually get62.5 m³/h
  • Head at the operating point27.5 m
  • Hydraulic power (water)4.68 kW
  • Shaft power at that point6.69 kW
  • Pump head at the flow you chose34.9 m
  • System head needed at the flow you chose20.1 m