Total Harmonic Distortion (THD) Calculator for Voltage and Current

THD from the fundamental and up to six harmonics, the same distortion against the total RMS value (THD-R), the total RMS and the largest single harmonic.

Results

THD (relative to the fundamental) 5.40 %
THD-R (relative to the total RMS) 5.39 %
Total RMS value 230.335
Largest harmonic as a share of the fundamental 3.91 %

What this tool does

THD is the RMS of all the harmonics divided by the fundamental, so a clean sine is 0 % and a heavily distorted current can pass 100 %. Standards use the fundamental as the reference (IEEE 519, IEC 61000), while some analysers also show THD-R against the total RMS, which cannot exceed 100 %. Enter the harmonics in the same unit as the fundamental, as RMS values or percentages — the result is the same. Public-supply standards such as EN 50160 limit the voltage THD to 8 %; current distortion limits depend on the size of the installation.

Formula

THD = √(H₂² + H₃² + … + Hₙ²) ÷ H₁ × 100 · THD-R = √(H₂² + …) ÷ √(H₁² + H₂² + …) × 100 · total RMS = √(H₁² + H₂² + …)

Variables

SymbolMeaningUnit
v1Fundamental (1st harmonic)—
h22nd harmonic—
h33rd harmonic—
h55th harmonic—
h77th harmonic—
h99th harmonic—
h1111th harmonic—
THTHD (relative to the fundamental)%
TRTHD-R (relative to the total RMS)%
TTTotal RMS value—
MXLargest harmonic as a share of the fundamental%

Worked example

  • Fundamental (1st harmonic)230
  • 2nd harmonic2
  • 3rd harmonic6
  • 5th harmonic9
  • 7th harmonic5
  • 9th harmonic2
  • 11th harmonic2
  • THD (relative to the fundamental)5.40 %
  • THD-R (relative to the total RMS)5.39 %
  • Total RMS value230.335
  • Largest harmonic as a share of the fundamental3.91 %

Limitations

  • The formula assumes ideal conditions: no friction losses, no air resistance and no efficiency losses unless you enter them.
  • For work that must comply with a standard or be signed off, check the result against the applicable code and have it reviewed by a qualified engineer.